HomeOIL WATER SEPARATORSeparator Alarm For Grease And Oil Separators Of ASA-01 Disconnection Alarm

Separator Alarm For Grease And Oil Separators Of ASA-01 Disconnection Alarm

Connected and EX-rated separator alarm for grease and oil separators. ASA-01 monitors layers, high levels and sludge with measuring sensors and sends values ​​to AfrisoCloud for remote reading, better control and more planned maintenance.

ASA-01 Disconnection Alarm is a pioneering solution for monitoring grease and oil separators in explosive environments. It offers a sophisticated electronics unit compatible with up to three digital measuring ASA sensors, providing comprehensive and reliable separator monitoring.

Separator Alarm For Grease And Oil Separators Variants

ASA-01 – measuring layer alarm
ASA-01 – measuring layer, high level and sludge alarm
ASA-01 – measuring layer and high level alarm

ASA-01 Disconnection Alarm Features And Benefits

Separator Alarm For Grease And Oil Separators
Separator Alarm For Grease And Oil Separators

Measuring layer sensor, ASA-MLP
Capacitive sensor that measures the oil or grease layer in the separator. The measured value makes it easier to follow the development over time and plan emptying before the alarm level is exceeded.

High level sensor, ASA-HLP
Ultrasonic sensor that monitors rising liquid level in the separator. High level may indicate clogging, blocked outlet or need for action.

Measuring sludge sensor, ASA-MSP
Ultrasonic sensor that measures the level of sludge, sand and other solid materials. The measured value provides better information for service, emptying and preventive maintenance.

Built-in cloud connectivity
ASA-01 has a built-in IoT gateway with connection to AfrisoCloud for remote reading of measurement values ​​and alarm status.

Why choose ASA-01 Disconnection Alarm 

Better remote control
Measurement values ​​from the separator can be monitored via AfrisoCloud, making it easier to detect changes without manual control on site.

More planned emptying and service
By following layer, high level and sludge levels over time, emptying and service can be planned based on the actual status in the separator.

Reduced risk of acute problems
Early indications of rising levels, clogging or increasing sludge make it possible to act before the problem leads to downtime, overfilling or unwanted emissions.

ASA-01 Disconnection Alarm Specifications

  • Housing: 175 x 125 x 75 mm (W x H x D), 0.75 kg, ABS plastic, IP 65
  • Front panel with integrated touch buttons and backlit LCD display
  • Cable connections: 2 cable glands and 3 knock-outs. (7-10 mm)
  • Power supply: AC 230 V
  • Relay outputs: 3 changeover programmable, AC 250V / 5A / 100VA
  • Ambient temperature: -20°C – +60°C
  • Alarm: Plain text via LCD display and acoustic alarm
  • IoT Gateway: LTE CAT M1 IoT Gateway with connection to AfrisoCloud
  • Ex certificate: DNV 23 ATEX 86944X, II (I) G [Ex ia Ga] IIA

ASA-01 Disconnection Alarm Accessories :

Measuring layer sensor ASA-MLP
Enclosure : 150 mm, Ø30 mm (measuring rod 400 mm), PEHD plastic, IP68
Sensor cable : 5 m oil-resistant, 2 x 0.75 mm2
Liquid temperature : -20°C – + 40°C
Ex certificate : DNV 23 ATEX 86944X
II 1 G Ex ia IIA T4 Ga

High level sensor ASA-HLP
Enclosure : 150 mm, Ø30 mm, PEHD plastic, IP68
Sensor cable : 5 m oil-resistant, 2 x 0.75 mm2
Liquid temperature : -20°C – + 40°C
Ex certificate : DNV 23 ATEX 86944X
II 1 G Ex ia IIA T4 Ga

Measuring sludge sensor ASA-MSP
Enclosure : 150 mm, Ø30 mm, PEHD plast, IP68
Sensor cable : 5 m oil-resistant, 2 x 0.75 mm2
Liquid temperature : -20°C – + 40°C
Ex certificate : DNV 23 ATEX 86944X
II 1 G Ex ia IIA T4 Ga

Read more : Separator Alarm For Grease And Oil Separators Of ASA-02 Disconnection Alarm